Primary Injection Test Set · Test & Measurement
PCT-1000
Compact, rugged primary current injection system for substations and switchgear — 0–1000 A AC output (parallel) / 0–500 A (series), 3 kVA capacity, smooth current adjustment with clear display, IP67-rated casing, built-in timer (1 ms resolution) and secondary 50 A injection.
0–1000 A AC (parallel)0–500 A AC (series)Capacity 3 kVA
Output 3 V / 6 VAccuracy 1.0%Timer 0.001–999.999 s
IP67 casingPortable on-siteSmooth current adjust
Key features
Powerful output
0–1000 A AC (parallel) or 0–500 A (series), 3 kVA capacity.
Easy control
Smooth, continuous current adjustment with clear display.
Tough enclosure
Engineered plastic casing, dust/waterproof to IP67.
Built-in timing
0.001–999.999 s with 1 ms resolution for trip timing.
Low distortion
Standard sine wave with <5% distortion.
Portable on-site
Shock/vibration damping design for transport.
Where the PCT-1000 excels
Circuit breakers
Primary injection and trip timing checks.
Over‑current relays
Primary tests of relay and recloser operation.
MCBs
Verification of magnetic trips at high current.
CT checks
Optional ratio verification (with external secondary meter).
Ranges & key specifications
| Parameter | Specification |
|---|---|
| Output current | 0–1000 A AC (parallel); 0–500 A AC (series) |
| Capacity | 3 kVA |
| Output voltage | 3 V (parallel); 6 V (series) |
| Input power | AC 220 V, 50 Hz single phase |
| Accuracy | 1.0% |
| Waveform | Standard sine; <5% distortion |
| Secondary injection | 50 A |
| Timer | 0.001–999.999 s; resolution 1 ms; error 0.005% range ±2 digits |
| Duty cycle | 2.5 min ON, 10 min OFF |
| Dimensions / mass | Main: 470×370×380 mm / ~40 kg; Accessory box: 430×350×130 mm / ~5.25 kg |
| Operating conditions | −15–40 °C; RH < 80% |
See datasheet for full specifications and conditions.
What’s in the box
Standard accessories
- High current 500 A output cables ×4
- Secondary current cable ×1
- Ground cable ×1
- Power cable ×1
- User guide
Items may vary by configuration.
Safety & Compliance
ENCLOSURE
Engineered plastic casing to IP67; shock/vibration damping.
WARRANTY
1‑year warranty (with product registration; see datasheet).
Downloads
Primary injection setup — PCT-1000
Basic current injection
- Connect the **PCT-1000** output to the bus/primary circuit via the high-current cables.
- Place a **CT** on the conductor or use an external ammeter rated for the expected current.
- Ramp current smoothly to target; verify device response per test plan.
Tip: Keep leads short and tight; monitor temperature; follow the duty cycle (2.5 min ON / 10 min OFF).
Trip timing with auxiliary contact
- Wire the breaker’s **auxiliary contact** to the PCT-1000’s **timer input**.
- Start injection; the timer begins with output and **stops** when the aux contact changes state.
- Record trip time; repeat as needed and compare against limits.
Tip: For inverse-time curves, step current and capture trip times per point.