ERT15 / ERT20C+

Clamp Grounding & Earth Tester

ERT20C+_H_Zhoo_1255
Innovative technique in Ground Resistance Testing; non-contact, safe and fast.

Earth Resistance Clamp Meter

A highly sophisticated ground clamp meter that measure earth resistance and current flow using clamp technology

The clamp-on ground testing technique used by the ERT series simplifies ground loop testing and enables non-intrusive leakage current measurement. The ERT-20C+ is able to measure the leakage current of ground wire, whilst both models can measure the integrated value of ground resistance and resistance field.

Max. Ground Resistance Measurement:

0.01Ω to 1200Ω

Max. Leakage Measurement:

0.00mA to 20.0A (ERT20C+ only)

ModelERT20C+ERT15
Clamp size65mm×32mmΦ32mm
Resistance Range0.01Ω-1200Ω 0.01Ω-200Ω
Min. Resolution0.001 Ω±(1%+0.01Ω)
Min. Accuracy±(1%+0.01Ω)±(1%+0.01Ω)
Current Range0.00mA-20.0A -
Current Res.0.05mA-
Current accuracy±2.5% ±1mA-

30-Days Protection

Money back guarantee (UK customers only)

24/7 Guarantee

Full after-sales support guarantee

1-Year Warranty

Available on all products

Ordering Information

Use the 6-digit code below when placing your order
Support
Extra information relating to this product

No optional accessories available

  • Utility Poles/Service Entrance or Meter
  • Street Lighting
  • Lightning Protection
  • Street Cabinets
  • Telephone Pedestals
  • Cell Towers (applications with buried ground ring) 
  • Pad Mounted Transformer
  • Pole Mounted Transformer

1-year warranty (subject to product registration with GPS LTD).

Visit www.gpslimited.com/register-product

Service and calibration available.

Please contact for more information

Require further assistance?

We are more than happy to help. Please choose the service you require below:

want more details?

Fill in your details and we'll be in touch