Substation & HV Asset Diagnostics

TTR-6300 Transformer Turns Ratio Tester

0.9 to 10000 · blind vector group · single, three-phase, Z-type, PT and CT

Measuring the ratio is the easy part. Knowing the vector group before you start is the part that fails, on an old transformer with a corroded nameplate. This one determines the group itself, then reports the ratio for each phase pair against the voltages you enter.

Download Datasheet

5 inch colour touchscreen · 500 groups over USB and Bluetooth · CAT III 600 V · part number 806300

GPS LTD TTR-6300 transformer turns ratio tester, front panel showing the six colour-coded high and low voltage terminals, the five inch touchscreen and the test keypad
TTR-6300 · 229 × 166 × 74 mm, 1.5 kg · test leads a further 1.7 kg

What one test tells you

Press test once and the instrument returns six things, not one. Entering the rated voltages and the tap spacing first is what turns a raw ratio into a pass, a percentage error and a tap number.

Turns ratio

The measured ratio itself, to four decimal places on the low ratios where a small deviation matters most.

Ratio error

Compared against the rated high and low voltages you enter, so the result is a percentage deviation rather than a number you have to check by hand.

Vector group

Reported as D-d-6 and the like on three-phase, alongside the ratio for each of AB/ab, BC/bc and CA/ca separately.

Tap position

Deduced from the ratio error and the tap spacing you enter, so a transformer left on the wrong tap shows up as a number rather than a puzzle.

Polarity and angle

Subtractive or additive, with the phase angle, on single-phase transformers and on instrument transformers.

Stored, then off-site

500 groups on the instrument, out over Type-C to the PC software for spreadsheet reports, or over Bluetooth to the app.

When the nameplate has gone

A conventional ratio test needs the vector group entered before it starts, which assumes you know it. On an old transformer with a corroded or missing nameplate, you do not. The blind test works it out instead.

Nameplate readable

Normal three-phase test

Enter the rated high and low voltages, the tap spacing and the vector group, then test. The instrument checks the measured ratio against what the nameplate claims and gives you the error and the tap.

High voltage side
D, Y, YN or ZN
Low voltage side
d, y or yn
Group
Entered, 0 to 11
Nameplate illegible

Three-phase blind test

Set either side, or both, to unknown and leave the group on automatic. The instrument determines the coupling and the group from the measurement itself, and reports it back alongside the three ratios.

High voltage side
Unknown may be selected
Low voltage side
Unknown may be selected
Group
Automatic, determined by the instrument

Z-type transformers have their own switch position for ratio and group, and single-phase units report polarity and phase angle rather than a group.

Check the resolution at your ratio

The headline 0.0001 is the finest resolution, not the resolution. It applies below a ratio of 10 and steps as the ratio climbs, so a distribution transformer at 1000:1 reads to 0.1. Find your ratio in the table rather than the headline.

Turns ratioResolutionAccuracy
0.9 to 100.0001±(0.2% + 2 digits)
10 to 1000.001±(0.2% + 2 digits)
100 to 10000.01±(0.2% + 2 digits)
1000 to 20000.1±(0.2% + 2 digits)
2000 to 100000.1±(0.5% + 2 digits)
10000 and above1Not specified

Accuracy carries a two digit term as well as the percentage. At or above a ratio of 10000 the instrument still reads, but no accuracy is specified for it.

Six terminals, five kinds of transformer

Three on the high voltage side and three on the low, colour coded so the connection order is unambiguous at the transformer. Every test type uses the same six.

A, B and C to UA, UB and UC · a, b and c to Ua, Ub and Uc
Single-phaseRatio and polarity, using the UA and UB terminals on the high side and Ua and Ub on the low.
Three-phaseRatio and vector group, all three phases connected, with each pair reported separately.
Z-typeZigzag windings, with ratio and group tested on their own switch position.
PT and CTInstrument transformers tested on the same terminals as a single-phase unit.

Two lead sets are supplied at 10 m per set, one for each side, which is what lets the instrument stand clear of a tank while both windings are connected.

Technical specifications

Ratio accuracy and resolution both depend on the ratio being measured; see the table above for the figure at your ratio.
Turns ratio0.9 to 10000 · resolution and accuracy both step with the ratio, see the table above
Test typesSingle-phase, three-phase and Z-type transformers · PT and CT · three-phase blind test
ReportedRatio · ratio error against the entered nameplate voltages · vector group · deduced tap position · polarity and phase angle
Vector groupsHigh voltage D, Y, YN or ZN · low voltage d, y or yn · groups 0 to 11, or determined by the instrument on a blind test
TerminalsSix: UA, UB and UC on the high voltage side, Ua, Ub and Uc on the low · overload check before every test
Display5 inch full colour touchscreen, 854 × 480, active area 108 × 65 mm · English interface · real-time battery indication
ControlsTouchscreen with a silicone keypad alongside · test, confirm, return, multiplex and four-way navigation keys
Memory500 groups stored on the instrument, with recall and review on screen
InterfacesUSB Type-C to the supplied PC software, which reads stored records and generates spreadsheet reports · Bluetooth to the Android app for wireless measurement
PowerRechargeable 9.6 V 3800 mAh lithium pack, charged from the supplied 14.8 V / 1.5 A charger · automatic shutdown settable from 1 to 30 minutes
ConsumptionAbout 2 W on standby at full brightness · 12 W maximum while measuring
SafetyIEC 61010-1 · CAT III 600 V · pollution degree 2 · IEC 61010-4-3, radiated field 1 V/m or below
InsulationAbove 10 MΩ at 500 V between circuit and housing · withstands AC 3700 V rms
EnvironmentOperating −10 to 40 °C · storage −20 to 60 °C · both below 70% RH
Dimensions · weight229 × 166 × 74 mm · 1.5 kg with battery · test leads a further 1.7 kg
Part number806300

What’s in the kit

  • TTR-6300 transformer turns ratio tester
  • Test leads, two sets, 10 m per set
  • Type-C data cable, 1 m
  • PC software on CD
  • Battery charger, 14.8 V / 1.5 A
  • Manual, warranty certificate and carry bag

Two lead sets, 10 m each

One set for the high voltage side and one for the low, colour coded to the A, B and C terminals. Ten metres per set is what lets the instrument sit clear of a tank while both windings stay connected, and it is why the leads weigh more than the instrument does.

Request a quote — TTR-6300

We’ll reply with pricing, lead time and options.

Request a calibration certificate

Send us the serial number and we’ll locate your certificate.

General enquiry

Ask us anything — sales, technical, or order related.

Request a Quote

We’ll reply with pricing, lead time and options.

We never share your details. By sending, you agree to be contacted about your enquiry.