Tan delta and capacitance of transformers, bushings, CVTs, capacitors and arresters, measured either side of the mains frequency so interference from live plant stays out of the result.
Part number 806900 · replaces the GPS-6800 · 35 kg
0.5 to 10 kV in 500 V steps from a 1500 VA source.
Tan δ to 0.001% and capacitance to 0.001 pF.
Mains interference from live plant filtered out.
CVT self-excitation, no 10 kV needed.
Tan delta shows moisture, ageing and local defects in insulation before they show anywhere else.
Winding insulation and bushing test taps, at commissioning and in preventive testing.
CTs and PTs, and CVT C1 and C2 by self-excitation, including on an earthed bus.
Capacitance and loss together, with inductive and resistive objects recognised automatically.
Insulating oil with an oil cup, solid materials with an electrode, and verification against a standard.
In a substation the 50 Hz field from energised equipment can swamp a test current of a few milliamps. In the 50D mode the TD-6900 measures at 45 Hz and 55 Hz, where its filtering passes only the test signal, and calculates the 50 Hz result.
Near power frequency tan δ changes steadily with frequency, so the two readings are close and the result stands for a 50 Hz test. The 60D mode does the same at 55 and 65 Hz for 60 Hz systems.
The same four connections are printed on the instrument’s panel.
Test current is measured at the low-voltage end of the test object through C4, so the reading excludes stray paths to earth. The usual choice for transformer bushings with a test tap, capacitors and CTs on the bench.
For equipment that cannot be lifted from earth. The test current returns through the HV lead itself, and its shield clip can guard out a branch that should not be measured.
CVT1 and CVT2 drive a secondary winding at low voltage and the CVT generates its own test voltage. One connection gives C1 and C2 with their tan δ, and no 10 kV leaves the instrument. Where the bus must stay earthed, the GSTg mode measures the top section by reverse connection with low-voltage shielding.
Pair the TD-6900 with an external high-voltage supply and standard capacitor, including a series resonant set. The instrument tracks the supply from 40 to 70 Hz and reads Cx and Cn through C4 and C3.
The output cuts off on a high-voltage short or breakdown, a poor earth trips the earth protection, and CVT tests run inside four voltage and current limits. On large test objects the output tracks the capacitance rise to hold the test voltage.
Capacitive objects show Cx and tan δ, inductive ones Lx and Q, and resistive ones Rx, with voltage, current, phase, power and frequency alongside. Units are chosen automatically.
The built-in thermal printer prints each result, automatically if you choose, and 100 results are stored with the date and time. An RS-232 port connects a computer.
Connect an oil cup to measure tan δ of insulating oil where the loss is 0.01% or more, or a solid-material electrode for insulation samples.
| High voltage output | 0.5 to 10 kV in 500 V steps (20 levels) · 1500 VA |
| Tan δ accuracy | ±(1.5% of reading + 0.06%) |
| Capacitance accuracy | ±(1.5% of reading + 5 pF) |
| Resolution | Tan δ 0.001% · capacitance 0.001 pF |
| Tan δ range | 0.01% to 100% |
| Capacitance, internal HV | 3 pF to 60,000 pF at 10 kV · 60 pF to 1 µF at 0.5 kV |
| Capacitance, external HV | 3 pF to 1.5 µF at 10 kV · 60 pF to 30 µF at 0.5 kV |
| Connections | UST · GST · CVT self-excitation · reverse connection with low-voltage shielding (GSTg) |
| Test frequency | Single 45, 50, 55, 60 or 65 Hz · dual 50D (45/55 Hz) or 60D (55/65 Hz) |
| Standard capacitor | Internal, or external with its parameters entered |
| External supply | Tracks 40 to 70 Hz, including series resonant supplies |
| CVT ratio test | Ratio 10 to 99,999, ±1% of reading · phase 0 to 359.9°, ±0.1° |
| Harmonic adaptation | ≤3% |
| Oil test | With an oil cup, positive connection, for losses ≥0.01% |
| Records | Backlit LCD · built-in thermal printer · 100 stored results with date and time · RS-232 |
| Power supply | 220 V AC ±10% · 50/60 Hz ±1 Hz · mains or generator |
| Operating conditions | −15°C to 50°C · relative humidity <80% |
| Dimensions / mass | 460 × 345 × 345 mm · 35 kg |
Tell us what you test and the voltage your procedure calls for.
The TD-6900 is now our tan delta tester and takes over from the GPS-6800. If you are moving test procedures or records across, talk to us and an engineer will help you set it up.
Our engineers are happy to help with connections, test voltages and lead times.
We’ll reply with pricing, lead time and options.
Send us the serial number and we’ll locate your certificate.
Ask us anything — sales, technical, or order related.
We never share your details. By sending, you agree to be contacted about your enquiry.