ACW 5 kV · DCW 6 kV · IR 10 GΩ · 16-step sequences
A bench safety tester for production lines and compliance work. AC withstand, DC withstand and insulation resistance run individually or chained into a single automatic sequence, so a unit is proved in one pass rather than three separate set-ups.
10 plans × 16 steps · arc detection at nine levels · GFI at 0.5 mA · Handler (PLC) and RS-232C

Proving a unit usually means a withstand test, then another, then an insulation check, each with its own connection. Chained into a plan they run as one sequence on one connection.
AC withstand, then re-cable and run DC withstand, then re-cable again for insulation resistance. Three connections, three chances to get one wrong, and three records to reconcile afterwards.
Chain the tests into a plan and the instrument runs them in order on a single connection. Every step carries its own function, voltage, limits, ramp and dwell, and the results are listed step by step at the end.
Rise, test and fall are set separately from 0.1 to 999.9 s, so a capacitive load can be ramped gently and still dwell only as long as the standard requires. A 25-way Handler port and an RS-232C SCPI command set let the line act on the verdict without an operator reading a meter.
Same case, display, interfaces, timing and protection throughout. They differ only in which of the three tests is fitted.
AC withstand, 5 kV
AC withstand at 5 kV and 20 mA. The straightforward choice where the standard calls for a dielectric strength test and nothing more.
AC and DC withstand
Adds DC withstand at 6 kV and 10 mA, for capacitive assemblies where a DC test avoids the charging current an AC test would draw.
AC, DC and insulation
Adds insulation resistance at 1 kV to 10 GΩ, so withstand and IR run in one sequence on the same connection.
The test functions are fitted at build and cannot be added later, so it is worth being sure before the order goes in. Insulation resistance is only available on the model that also has DC withstand, so choosing IR brings both. Tell us the standard you test to and we will confirm the model.
Five kilovolts on a production line is a hazard whoever is holding the part. These are the things that stop the output without waiting for a person.
More than 0.5 mA returning through the chassis and the output is killed within 0.3 s, with GFI on the display. It can be switched off; it is worth leaving on.
Nine levels on both AC and DC, at 20, 18, 16, 14, 12, 10, 7.7, 5.5 and 2.8 mA, so sensitivity is set to a real current rather than a vague scale.
Trips at twice rated output current, or 1.5 times peak on AC.
After every test, 0.2 s, enough to bring 1 µF charged at 6 kV down to 30 V before anyone touches anything.
Upper and lower current limits give HI FAIL and LOW FAIL, with PASS, FAIL and TEST lamps and a beeper. The instrument decides, not the operator.
Above 6 mA AC or 3 mA DC, limit output to one minute and rest at least as long again.
The Handler port carries INTERLOCK, so a guard or a fixture lid can hold the output off as a condition of the test running at all.
Voltage resolution is 1 V throughout. Which groups apply depends on the model fitted.
| Parameter | Range | Resolution | Accuracy |
|---|---|---|---|
| AC withstand voltage · all models | |||
| Output voltage | 0.050 to 5.000 kV | 1 V | ±(2% rdg + 5 digits) |
| Test current | 0.001 to 20.00 mA | 0.001 / 0.01 mA | ±(2% rdg + 5 digits) |
| Frequency | 50 or 60 Hz | — | ±0.1% |
| Output waveform | Sine | — | Distortion below 3%, resistive load |
| Load regulation | No load to full load | — | ±(2% rdg + 5 V) |
| DC withstand voltage · GPS-9020AD and 9020ADI | |||
| Output voltage | 0.050 to 6.000 kV | 1 V | ±(2% rdg + 5 digits) |
| Test current | 0.1 µA to 10.00 mA | 0.1 µA / 0.01 mA | ±(2% rdg + 5 digits) |
| Insulation resistance · GPS-9020ADI | |||
| Output voltage | 0.050 to 1.000 kV | 1 V | ±(1% rdg + 2 digits) |
| Measuring range | 0.02 MΩ to 10 GΩ | — | Depends on test voltage, see below |
| Current range | Auto, or 1 µA to 5 mA fixed | — | Fixed ranges speed the test up |
| Timing · all models | |||
| Rise and fall | 0.1 to 999.9 s each, or off | — | — |
| Test time | 0.2 to 999.9 s ACW · 0.1 to 999.9 s DCW and IR, or unlimited | — | — |
Insulation accuracy depends on the test voltage. At 500 V and above, 1 MΩ to 1 GΩ is ±(5% rdg + 5 digits) and 1 to 10 GΩ is ±(10% rdg + 5 digits). Below 500 V, 0.1 MΩ to 1 GΩ is ±(10% rdg + 5 digits), and the 1 to 10 GΩ band is indicative only with no accuracy specified. Auto ranging adds switching time, so a test takes at least one second.
| Tests | AC withstand on all models · DC withstand on the AD and ADI · insulation resistance on the ADI · fitted at build and not addable later |
|---|---|
| Test plans | 10 stored internally, up to 16 steps each · every step has its own function, voltage, limits, timing and arc level |
| Display | 5 inch colour touch LCD with a 32-bit ARM processor · keypad and cursor keys · English interface |
| Accounts | Administrator and operator · operator changes are not saved |
| Judgement | Upper and lower current limits, HI FAIL and LOW FAIL · short-circuit trip · PASS, FAIL and TEST lamps with beeper |
| Results | Listed step by step at the end of a run, and recallable from the data record |
| Handler (PLC) | 25-way: START, STOP, TEST, PASS, FAIL, INTERLOCK · +24 V at up to 1 A for lamps and solenoids |
| RS-232C | 8 data bits, 1 stop bit, no parity · SCPI command set · DB-9 straight-through, 2 m maximum |
| File storage | 10 files internally, or to a USB stick on the front panel |
| Protection | Ground fault interrupter at 0.5 mA, output off within 0.3 s · arc detection, nine levels · short-circuit trip · automatic discharge, 0.2 s |
| Power | 110 V or 220 V AC ±10%, rear panel switch · 300 VA maximum · fuse 5 A at 110 V, 3 A at 220 V |
| Environment | Operating 10 to 40 °C at 10 to 80% RH · specified 18 to 28 °C · altitude to 2000 m |
| Duty cycle | Above 6 mA AC or 3 mA DC, limit to one minute on and rest as long again |
| Dimensions · weight | 293.8 × 130 × 447.9 mm with handle · 246 × 112 × 422.3 mm without · about 8 kg |
| Part numbers | GPS-9020A 869020 · GPS-9020AD 869068 · GPS-9020ADI 869164 |
One set for the high voltage side and one for the low, colour coded to the A, B and C terminals. Ten metres per set is what lets the instrument sit clear of a tank while both windings stay connected, and it is why the leads weigh more than the instrument does.
We’ll reply with pricing, lead time and options.
Send us the serial number and we’ll locate your certificate.
Ask us anything — sales, technical, or order related.
We never share your details. By sending, you agree to be contacted about your enquiry.